Recommended Max PV input power
7500W/9000W/12000W/15000W
Max. input voltage
1000V
Start-up voltage
180V
Rated input voltage
620V
MPPT operating voltage range
200V-850V
Number of MPP trackers
2
Max number of input strings per MPPT
1
Max input current per MPPT
16A
Max short circuit current per MPPT
21.2A
AC output (Grid)-Rated output power
5000W/6000W/8000W/10000W
Rated output current
7.3A/8.7A/11.6A/14.5A
Rated grid voltage
400V/380V, 3L/N/PE
Rated grid frequency
50Hz/60Hz
Max output apparent power
5500VA/6600VA/8800VA/11000VA
Max output current
8.4A/10A/13.4A/16.5A
Max. Current from grid
11.5A/13.6A/18.2A/22.7A
THDI
<3%
Power factor
1 (0.8 leading - 0.8 lagging)
Battery type
Li-ion(LFP)
Battery voltage range
180V-600V
Number of battery input channels
1
Max charge/discharge power
7500W/8450W/9600W/10000W
Max. charge/discharge current
25A/25A
BMS communication
CAN/RS485
AC output (Backup)-Rated output power
5000W/6000W/8000W/10000W
Rated output current
7.3A/8.7A/11.6A/14.5A
Rated output voltage
400V/380V, 3L/N/PE
Rated output frequency
50Hz/60Hz
Max. output apparent power
5000VA/6000VA/8000VA/10000VA
Peak output apparent power, time
1.1x, 10min
Max. output current
8.4A/10A/13.4A/16.5A
THDV linear load
<3%
Switching time
<10ms
Max MPPT efficiency
99.9%
Max efficiency
98.2%
European efficiency
97.2%/97.2%/97.5%/97.5%
Max. efficiency of charging/discharging
97.5%
DC switch
Integrated
PV reverse connection protection
Integrated
Battery reverse connection protection
Integrated
Output short circuit protection
Integrated
Output overcurrent protection
Integrated
Output overvoltage protection
Integrated
Insulation Impedance detection
Integrated
Residual current detection
Integrated
Anti-island protection
Integrated
Surge protection
DC/AC
AFCI
Optional
Operating temperature range
-35°C~+60°C
Relative humidity range
0-95%
Max operating altitude
4000m (with derating above 2000m)
Standby self-consumption
<15W
Topology
Non-isolated
Installation method
Wall Mounting
Degree of protection
IP66
Dimensions (WHD)
475mm535mm205mm
Cooling mode
Natural Cooling
Weight
30kg
Communication
CAN/RS485
Display
LED APP/LCD (optional)
Safety EMC
EN 62109-1&2; EN61000-6-1, EN 61000-6-3