AC-DC Rectifier

Cost-effectiveness, Service Response, Flexible Configuration, Smart Management, Efficient Implementation

Advantages

Sma Management

Input mode
380VAC (three-phase five-wire) / 220VAC (Single-phase three-wire)
Input circuit breaker
1x63/4p
Input frequency
45~65Hz,Rating: 50Hz/60HZ
AC lightning protection
20kA/40kA,8/20us
Output voltage
-42~-58VDC,Rating: 53.5VDC
Maximum power
20kW
Battery circuit breaker
2x125/3 p
Load circuit breaker
LL VD:25A/1Px5+63A/1Px4; BL VD:10A/1PX4+32A/1Px2
Module efficiency
≤96%
DI/DO
3*AI (2 * Battery temperature, 1*Ambient temperature), 7*DI, 6*DO, 2*RS485, 1*SPD, 12VDC interface
Operating temperature range
-40°C~+65°C
Operating humidity range
5%~95%
Altitude
0~4000m (When the altitude is between 3000m and 4000m, the max operating temperature decreases by 1°C for every 200m increase in altitude)

Providing materials on selection, installation, and O&M

Backup Battery
1.71 MB | PDF